Hollis & Pike Mechanicals

Daikin

Daikin VRV IV RXYTQ8T7YF

VRF / VRV outdoor unit

System family
daikin_vrv4_r410a_t3
Nominal cooling capacity
22.4 kW
Cooling capacity at T3 (46 °C)
20.2 kW
Nominal heating capacity
22.4 kW
Power input (cooling)
6.33 kW
Rating standard
Ahri 1230
AvailabilitySpecial order· Lead time 6 weeks

Budget prices and project quotations come from Henrik and our regional teams.

Overview

VRV IV T3 heat pump, 8 HP: 22.4 kW at T1 (35 °C, AHRI 1230) and 20.2 kW at T3 (46 °C, ISO 15042 / ESMA); EER 12.1 Btu/h/W (3.55 W/W) at T1, 9.28 Btu/h/W (2.72 W/W) at T3; one compressor; 3-phase 380–415 V.

Documents

Technical Data

Identity

System familydaikin_vrv4_r410a_t3

Capacity

Nominal cooling capacity22.4 kW
Cooling capacity at T3 (46 °C)20.2 kW
Nominal heating capacity22.4 kW
Power input (cooling)6.33 kW
Rating standardAhri 1230
Climate classT3

Efficiency

EER (standard condition)3.55
EER at T3 (46 °C)2.72
COP (heating)4.31

Refrigeration

RefrigerantR410A
Inverter compressorYes
Number of compressors1

Refrigerant piping

Liquid pipe diameter9.52 mm
Gas pipe diameter19.1 mm
Max total pipe length1000 m

VRF system

Pipe systemTwo pipe heat pump
Capacity index200
Outdoor unit size8 HP
Max connectable indoor units64
Min connection ratio50 %
Max connection ratio130 %

Electrical

Nominal voltage400 V
Power supplyThree
Frequency50

Acoustics

Sound pressure58 dB(A)
Sound power78 dB(A)

Operating envelope

Min outdoor temperature (cooling)-5 °C
Max outdoor temperature (cooling)55 °C

Physical

Height1685 mm
Width930 mm
Depth765 mm
MountingPad
Corrosion protectionCoastal coated

Suitability

Used in / applicationsOffice, Retail, Hotel hospitality, Residential villa, High rise, Healthcare

Commercial

Country of originJapan

Data from the manufacturer's published documentation. Confirm selection data against the current datasheet before specification.

SAME RANGE

More VRF Systems

View all
Ask about this unit