Hollis & Pike Mechanicals

Daikin

Daikin VRV IV RXYTQ10T7YF

VRF / VRV outdoor unit

System family
daikin_vrv4_r410a_t3
Nominal cooling capacity
28.0 kW
Cooling capacity at T3 (46 °C)
25.2 kW
Nominal heating capacity
28.0 kW
Power input (cooling)
7.47 kW
Rating standard
Ahri 1230
AvailabilitySpecial order· Lead time 6 weeks

Budget prices and project quotations come from Henrik and our regional teams.

Overview

VRV IV T3 heat pump, 10 HP: 28.0 kW at T1 (35 °C, AHRI 1230) and 25.2 kW at T3 (46 °C, ISO 15042 / ESMA); EER 12.8 Btu/h/W (3.75 W/W) at T1, 9.90 Btu/h/W (2.90 W/W) at T3; one compressor; 3-phase 380–415 V.

Documents

Technical Data

Identity

System familydaikin_vrv4_r410a_t3

Capacity

Nominal cooling capacity28.0 kW
Cooling capacity at T3 (46 °C)25.2 kW
Nominal heating capacity28.0 kW
Power input (cooling)7.47 kW
Rating standardAhri 1230
Climate classT3

Efficiency

EER (standard condition)3.75
EER at T3 (46 °C)2.9
COP (heating)4.19

Refrigeration

RefrigerantR410A
Inverter compressorYes
Number of compressors1

Refrigerant piping

Liquid pipe diameter9.52 mm
Gas pipe diameter22.2 mm
Max total pipe length1000 m

VRF system

Pipe systemTwo pipe heat pump
Capacity index250
Outdoor unit size10 HP
Max connectable indoor units64
Min connection ratio50 %
Max connection ratio130 %

Electrical

Nominal voltage400 V
Power supplyThree
Frequency50

Acoustics

Sound pressure61 dB(A)
Sound power81 dB(A)

Operating envelope

Min outdoor temperature (cooling)-5 °C
Max outdoor temperature (cooling)55 °C

Physical

Height1685 mm
Width1240 mm
Depth765 mm
MountingPad
Corrosion protectionCoastal coated

Suitability

Used in / applicationsOffice, Retail, Hotel hospitality, Residential villa, High rise, Healthcare

Commercial

Country of originJapan

Data from the manufacturer's published documentation. Confirm selection data against the current datasheet before specification.