Carrier
Carrier 42C/D 42CET006
Fan coil unit
- Nominal cooling capacity
- 4.99 kW
- Indoor unit type
- Ducted medium static
- Sound pressure (low / quiet mode)
- 35.4 dB(A)
- Airflow (nominal / high)
- 846 m³/h
- Airflow (low)
- 500 m³/h
- External static pressure
- 50 Pa
AvailabilityOut of stock· Lead time 3 weeks
Budget prices and project quotations come from Henrik and our regional teams.
Technical Data
Capacity
| Nominal cooling capacity | 4.99 kW |
|---|
Indoor unit
| Indoor unit type | Ducted medium static |
|---|---|
| Sound pressure (low / quiet mode) | 35.4 dB(A) |
Air performance
| Airflow (nominal / high) | 846 m³/h |
|---|---|
| Airflow (low) | 500 m³/h |
| External static pressure | 50 Pa |
| Fan motor | Ac multi speed |
Hydronic
| Water flow | 0.21 l/s |
|---|---|
| Water pressure drop | 9.3 kPa |
| Entering water temperature | 7.2 °C |
| Leaving water temperature | 12.8 °C |
| Pipe connection | 3/4 in FPT (BSP) brass |
Electrical
| Power supply | Single |
|---|---|
| Frequency | 50 |
| Rated power | 114 W |
| Rated current | 0.5 A |
Acoustics
| Sound pressure | 40.4 dB(A) |
|---|
Physical
| Height | 241 mm |
|---|---|
| Width | 557 mm |
| Depth | 1170 mm |
| Weight | 23.7 kg |
| Casing material | Galvanised steel |
| Mounting | Ceiling recessed |
Suitability
| Used in / applications | Hotel hospitality, Residential apartment, Office, Healthcare, Education |
|---|
Commercial
| Warranty | 2 years |
|---|---|
| Country of origin | United States |
Data from the manufacturer's published documentation. Confirm selection data against the current datasheet before specification.