Hollis & Pike Mechanicals
Belimo 22DC-13

Belimo

Belimo 22DC-13

Sensor

Sensor type
Co2
Measuring range
0...2000 ppm (0...5000 ppm with accessory A-22G-A05)
Accuracy
±(50 ppm + 3% of measured value)
Output signal
Active 4 20ma, Active 0 10v
Nominal voltage
24 V
Rated power
2.3 W
AvailabilityLimited stock· Lead time 2 days

Budget prices and project quotations come from Henrik and our regional teams.

Overview

Active duct CO₂ sensor with self-calibrating dual-channel NDIR element, 150 mm probe, 4...20 mA or 0...5/10 V output, for duct air velocities of 0.3...12 m/s, IP65 / NEMA 4X housing.

Documents

Technical Data

Sensor

Sensor typeCo2
Measuring range0...2000 ppm (0...5000 ppm with accessory A-22G-A05)
Accuracy±(50 ppm + 3% of measured value)
Output signalActive 4 20ma, Active 0 10v

Electrical

Nominal voltage24 V
Rated power2.3 W
IP ratingIP65

Physical

Weight0.26 kg
Colourorange
MountingDuct inline

Compliance & certifications

CertificationsCE, Ul, Iso 9001

Suitability

Used in / applicationsOffice, Education, Hotel hospitality, Healthcare, Retail

Commercial

Warranty2 years
Country of originSwitzerland

Data from the manufacturer's published documentation. Confirm selection data against the current datasheet before specification.

SAME RANGE

More Controllers & Sensors

View all
Ask about this unit